Heat-glo-fireplace Heat & Glo Fireplace 8000TVC Manuel d'utilisateur Page 12

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 25
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 11
9
C. Bedroom Installation in Canada
This model MUST NOT be vented into a vent
system installed exterior to a building. The part of
the vent system above the roof line can be exterior
to the building.
D. Vent Termination
WARNING: MAJOR U.S. BUILDING
CODES SPECIFY MINIMUM
CHIMNEY AND/OR VENT HEIGHT
ABOVE THE ROOF TOP. THESE
MINIMUM HEIGHTS ARE
NECESSARY IN THE INTEREST OF
SAFETY. FIGURE 6 AND TABLE
SHOW MINIMUM HEIGHTS,
PROVIDED THE TERMINATION CAP
IS AT LEAST 8-FEET FROM A
VERTICAL WALL.
ROOF PITCH H (MIN.) FT.
FLAT TO 6/12 1.0
6/12 TO 7/12 1.25
OVER 7/12 TO 8/12 1.5
OVER 8/12 TO 9/12 2.0
OVER 9/12 TO 10/12 2.5
OVER 10/12 TO 11/12 3.25
OVER 11/12 TO 12/12 4.0
OVER 12/12 TO 14/12 5.0
OVER 14/12 TO 16/12 6.0
OVER 16/12 TO 18/12 7.0
OVER 18/12 TO 20/12 7.5
OVER 20/12 TO 21/12 8.0
Figure 6. Vent Termination
H (MIN.)-MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
H (MIN.)-MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
VENT CAP
LOWEST DISCHARGE OPENING
12
X
ROOF PITCH IS X/12
Vue de la page 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 24 25

Commentaires sur ces manuels

Pas de commentaire